-40%

Altronix eFlow4N8 Multi-Output Power Supply/Charger  12/24 VDC, eFlow 4N8

$ 52.77

Availability: 56 in stock
  • Restocking Fee: No
  • Return shipping will be paid by: Buyer
  • Condition: New
  • Custom Bundle: No
  • Brand: Altronix
  • Refund will be given as: Money Back
  • Country/Region of Manufacture: USA
  • Model: eFlow4N8
  • All returns accepted: Returns Accepted
  • Type: Fire Alarms
  • Item must be returned within: 30 Days
  • Modified Item: No
  • MPN: EFLOW4NA8

    Description

    Altronix eFlow4N8 Multi-Output Power Supply/Charger  12/24 VDC.
    Altronix eFlow4N8 is a power supply/charger converts a 120VAC 60Hz input into a eight (8) fuse Class 2 power-limited outputs. Power supply/charger is selectable for 12VDC or 24VDC with a total of 4A max. It also offers a suite of features that includes fire alarm disconnect, overvoltage protection, and low power disconnect which prevents deep discharge of stand-by batteries.
    Input
    120VAC, 60Hz, 3.5A.
    Input fuse: 5A/250V.
    Output
    Eight (8) Class 2 power-limited fuse protected outputs.
    12VDC or 24VDC selectable output.
    12VDC or 24VDC @ 4.0A supply current.
    Outputs are rated @ 2.5A.
    Auxiliary Class 2 power-limited output rated @ 1A (unswitched).
    Overvoltage Protection.
    Battery Backup
    Built-in charger for sealed lead acid or gel type batteries.
    Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
    Supervision
    AC fail supervision (form "C" contacts).
    Notification trigger is selectable for 30 seconds (factory set) or 2 hours.
    Battery fail & presence supervision (form "C" contacts).
    Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
    Fire Alarm Disconnect
    Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
    Electrical
    Temperature:
    Operating: 0° C to 49° C (32° F to 120° F).
    Storage: - 20° C to 70° C ( - 4° F to 158° F).
    Relative Humidity 85% +/- 5%.
    BTU/Hr (approx.):
    12VDC: 12 BTU/Hr.
    24VDC: 49 BTU/Hr.
    System AC input VA requirement: 420VA.
    Visual Indicators
    Green AC Power LED indicates 120VAC present.
    AC input and DC output LED indicators.
    Additional Features
    Short circuit and overload protection.
    Unit is complete with power supply, enclosure, battery leads and cam lock.